UP900-G4 SERIES
6kVA-10kVA
UP900-G4 series is suitable where long back times are required for 1- 8 hours. The UP900-G4 is single-phase and offers the highest power availability with an output power factor of 1 (kVA=KW). The wide input voltage range means that UPS can guarantee a 100% stable output without using the battery for AC voltages of 176Vac to 288Vac.
Areas of Usage
- General Description
- Technical Specifications
- Documents
6kVA – 10kVA The UP900-G4 series is suitable where long back times are required for 1- 8 hours. The UP900-G4 offers the highest power availability with an output power factor of 1 (kVA = KW). The wide input voltage range means that UPS can guarantee a 100% stable output without using the battery for AC voltages of 176Vac to 288Vac.
|
- UP906-G4
- UP910-G4
TECHNICAL SPECIFICATIONS UP906-G4 | 6kVA |
|||
MODEL |
UP906-G4 |
||
Capacity |
6 kVA / 6 kW |
||
INPUT |
|||
Input wiring |
Single-phase three-wire (1 Φ + N + PE) |
||
Rated Voltage |
208 / 220 / 230 / 240 Vac |
||
Voltage range |
110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 288 Vac (no derating) |
||
Rated frequency |
50 / 60 Hz (auto-sensing) |
||
Frequency range |
40 ~ 70 Hz |
||
|
Power factor |
≥0.99 |
|
Bypass voltage range |
– 40% ~ +15% (settable) |
||
|
Total harmonic distortion (THDi) |
≤ 5% |
|
OUTPUT |
|||
Output wiring |
Single-phase three-wire (1 Φ + N + PE) |
||
Rated Voltage |
208 (PF=0.9) / 220 / 230 / 240 Vac |
||
Voltage regulation |
+ 1% |
||
Frequency |
Synchronized to bypass in mains mode; 50 / 60 Hz±0.1 % Hz in battery mode |
||
Waveform |
Sinusoidal |
||
Power factor |
1 |
||
Total harmonic distortion |
≤ 1 % (linear load); ≤ 4% (non-linear load) |
||
Crest factor |
3:1 |
||
Overload |
105% ~ 110%for 10 min, 110% ~ 125% for 1 min, 126% ~ 150% for 30 s |
||
BATTERIES |
|||
DC voltage |
192 Vdc (192 -240 Vdc settable) |
||
Number of batteries |
16 pcs (16 -20 settable) |
||
Inbuilt battery (standard model) |
12V/7Ah x16 |
||
Charging Current |
Standard model: 1 A; |
||
Recharge time |
Standard model: 90% capacity restored in 8 hours |
||
SYSTEM |
|||
Efficiency |
≥94% at 100% load, max. 95% at 60% load, ≥98% in ECO mode |
||
Transfer time |
0 ms |
||
Protections |
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
||
Max. number of parallel connections |
4 |
||
Communications |
RS232 (standard), USB / RS485 / dry contacts/ SNM P / battery temperature compensation (optional) |
||
Display |
LCD+ LED |
||
OTHER |
|||
Operating temperature |
0 – 40°C |
||
Storage temperature |
25° ~ 55°C (without battery) |
||
Relative Humidity |
0 ~ 95% (non-condensing) |
||
Altitude |
≤ 1000 m, derating 1 % for each additional 100 m |
||
IP rating |
IP 20 |
||
Noise level at 1m |
≤ 55 dB |
||
Dimensions WxDxH (mm) |
191 x 465 x 711 (S) , 191 x 465 x 350 (H) |
||
Net Weight (Kgs) |
53 (S) , 14.5 (H) |
||
Gross Weight (Kgs) |
61 (S), 16 (H) |
||
S means standard model; H means long time model. |
TECHNICAL SPECIFICATIONS UP910-G4 | 10kVA |
|||
MODEL |
UP910-G4 |
||
Capacity |
10 kVA / 10 kW |
||
INPUT |
|||
Input wiring |
Single-phase three-wire (1 Φ + N + PE) |
||
Rated Voltage |
208 / 220 / 230 / 240 Vac |
||
Voltage range |
110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 288 Vac (no derating) |
||
Rated frequency |
50 / 60 Hz (auto-sensing) |
||
Frequency range |
40 ~ 70 Hz |
||
|
Power factor |
≥0.99 |
|
Bypass voltage range |
– 40% ~ +15% (settable) |
||
|
Total harmonic distortion (THDi) |
≤ 5% |
|
OUTPUT |
|||
Output wiring |
Single-phase three-wire (1 Φ + N + PE) |
||
Rated Voltage |
208 (PF=0.9) / 220 / 230 / 240 Vac |
||
Voltage regulation |
+ 1% |
||
Frequency |
Synchronized to bypass in mains mode; 50 / 60 Hz±0.1 % Hz in battery mode |
||
Waveform |
Sinusoidal |
||
Power factor |
1 |
||
Total harmonic distortion |
≤ 1 % (linear load); ≤ 4% (non-linear load) |
||
Crest factor |
3:1 |
||
Overload |
105% ~ 110%for 10 min, 110% ~ 125% for 1 min, 126% ~ 150% for 30 s |
||
BATTERIES |
|||
DC voltage |
192 Vdc (192 -240 Vdc settable) |
||
Number of batteries |
16 pcs (16 -20 settable) |
||
Inbuilt battery (standard model) |
12V/9Ahx16 |
||
Charging Current |
Standard model: 1 A; |
||
Recharge time |
Standard model: 90% capacity restored in 8 hours |
||
SYSTEM |
|||
Efficiency |
≥94% at 100% load, max. 95% at 60% load, ≥98% in ECO mode |
||
Transfer time |
0 ms |
||
Protections |
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
||
Max. number of parallel connections |
4 |
||
Communications |
RS232 (standard), USB / RS485 / dry contacts/ SNM P / battery temperature compensation (optional) |
||
Display |
LCD+ LED |
||
OTHER |
|||
Operating temperature |
0 – 40°C |
||
Storage temperature |
25° ~ 55°C (without battery) |
||
Relative Humidity |
0 ~ 95% (non-condensing) |
||
Altitude |
≤ 1000 m, derating 1 % for each additional 100 m |
||
IP rating |
IP 20 |
||
Noise level at 1m |
≤ 58 dB |
||
Dimensions WxDxH (mm) |
191 x 495 x 711 (S), 191 x 495 x 350 (H) |
||
Net Weight (Kgs) |
62 (S), 16.5 (H) |
||
Gross Weight (Kgs) |
70 (S). 18 (H) |
||
S means standard model; H means long time model. |