3 Phase online UPS
UPS | MY-UP300 SERIES 10-200 kVA
3 Phase: 10kVA - 200kVA
Firstly the NEW 3-phase MY-UP300 Series offers excellent protection against energy quality problems in addition to using the latest technologies to improve performance and security. Secondly it has wide input voltage and frequency range as well as high grid adaptability and finally prolonged battery life, all making this UPS reliable and extremely powerful. The advanced dual DSP control prevents single failure point and increases its performance.
Areas of Usage
- General Description
- Technical Specifications
- Documents
The 3-phase MY-UP300 series is a modern high-frequency design UPS is suitable for a wide range of applications such as telecoms, local area networks, e-business, data-centres, cash registers and security. The 3-Phase MY-UP300 series conforms to the following standards: ISO9001 GENERAL SPECIFICATIONS:
|
- MY-UP300 SERIES (10-40 kVA)
- MY-UP300 SERIES (60-200 kVA)
- MYUP300 10kVA
- MYUP300 15kVA
- MYUP300 20kVA
- MYUP300 30kVA
- MYUP300 40kVA
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
||||
MODEL |
MY-UP300 10kVA |
|||
INPUT | ||||
Voltage (VAC) |
80-280 (L-N)/138-485 (L-L) |
|||
Phase |
1:1/3:1/3:3 |
|||
Frequency | 40-70 | |||
Power Factor |
≥0.99 |
|||
THDi |
<3% | |||
Dual Main Input |
Yes |
|||
OUTPUT | ||||
AC/AC Efficiency (Max.) |
96% |
|||
Power Factor |
1.0 |
|||
Voltage (VAC) |
220/230/240±1% (L-N) 380/400/415±1% (L-L) |
|||
Frequency (Hz) |
50/60±0.1 (battery mode) |
|||
THDv |
THD <1% (linear load), THD <3% (nonlinear load) |
|||
Crest Factor |
3:1 |
|||
Overload¹ |
110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms |
|||
EPO |
Remote and Local |
|||
Coldstart |
Yes |
|||
BATTERY | ||||
Voltage (Vdc) | ±192 (±96 ~±240 adjustable) | |||
Internal Battery | 16~40×9AH/12V | |||
Charging Current (A) | 1-10 settable | |||
OTHER | ||||
Communication Interface | RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot) | |||
Display | 4.3 Inch Touch Screen+ LED+ Physical buttons | |||
Alarm | Low battery, abnormal AC input, UPS failure, etc. | |||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||
Noise (dB) | <55 | |||
Working Temperature | -5~40 | |||
Altitude | 2000, no derate | |||
Relative Humidity | 0 ~ 95%, no condensation | |||
Dimensions (WxDxH) (mm) | 250×755×880 | |||
Weight |
with battery | 98 (20×7AH) | ||
without battery | 50 | |||
witht TX | 143 | |||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
||||
MODEL |
MY-UP300 15kVA |
|||
INPUT | ||||
Voltage (VAC) |
80-280 (L-N)/138-485 (L-L) |
|||
Phase |
1:1/3:1/3:3 |
|||
Frequency | 40-70 | |||
Power Factor |
≥0.99 |
|||
THDi |
<3% | |||
Dual Main Input |
Yes |
|||
OUTPUT |
AC/AC Efficiency (Max.) |
96% |
||
Power Factor |
1.0 |
|||
Voltage (VAC) |
220/230/240±1% (L-N) 380/400/415±1% (L-L) |
|||
Frequency (Hz) |
50/60±0.1 (battery mode) |
|||
THDv |
THD <1% (linear load), THD <3% (nonlinear load) | |||
Crest Factor |
3:1 |
|||
Overload¹ |
110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms |
|||
EPO |
Remote and Local |
|||
Coldstart |
Yes |
|||
BATTERY | ||||
Voltage (Vdc) | ±192 (±144 ~±240 adjustable)* | |||
Internal Battery | 24~40×9AH/12V | |||
Charging Current (A) | 1-10 settable | |||
OTHER | ||||
Communication Interface | RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot) | |||
Display | 4.3 Inch Touch Screen+ LED+ Physical buttons | |||
Alarm | Low battery, abnormal AC input, UPS failure, etc. | |||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||
Noise (dB) | <55 | |||
Working Temperature | -5~40 | |||
Altitude | 2000, no derate | |||
Relative Humidity | 0 ~ 95%, no condensation | |||
Dimensions (WxDxH) (mm) | 250×755×880 | |||
Weight (Kg) | with battery | 127 (32×9AH) | ||
without battery | 50 | |||
witht TX | 143 | |||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
||||
MODEL |
MY-UP300 20kVA |
|||
INPUT | ||||
Voltage (VAC) |
80-280 (L-N)/138-485 (L-L) |
|||
Phase |
1:1/3:1/3:3 |
|||
Frequency | 40-70 | |||
Power Factor |
≥0.99 |
|||
THDi |
<3% | |||
Dual Main Input |
Yes |
|||
OUTPUT | ||||
AC/AC Efficiency (Max.) |
96% |
|||
Power Factor |
1.0 |
|||
Voltage (VAC) |
220/230/240±1% (L-N) 380/400/415±1% (L-L) |
|||
Frequency (Hz) |
50/60±0.1 (battery mode) |
|||
THDv |
THD <1% (linear load), THD <3% (nonlinear load) |
|||
Crest Factor |
3:1 |
|||
Overload¹ |
110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms |
|||
EPO |
Remote and Local |
|||
Coldstart |
Yes |
|||
BATTERY | ||||
Voltage (Vdc) | ±192 (±144 ~±240 adjustable)* | |||
Internal Battery | 24~40×9AH/12V | |||
Charging Current (A) | 1-10 settable | |||
OTHER | ||||
Communication Interface | RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot) | |||
Display | 4.3 Inch Touch Screen+ LED+ Physical buttons | |||
Alarm | Low battery, abnormal AC input, UPS failure, etc. | |||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||
Noise (dB) | <55 | |||
Working Temperature | -5~40 | |||
Altitude | 2000, no derate | |||
Relative Humidity | 0 ~ 95%, no condensation | |||
Dimensions (WxDxH) (mm) | 250×755×880 | |||
Weight |
with battery | 144 (40×9AH) | ||
without battery | 50 | |||
witht TX | 143 | |||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
||||
MODEL |
MY-UP300 30kVA |
|||
INPUT | ||||
Voltage (VAC) |
138-485 (L-L) |
|||
Phase |
3:1/3:3 |
|||
Frequency | 40-70 | |||
Power Factor |
≥0.99 |
|||
THDi |
<3% | |||
Dual Main Input |
Yes |
|||
OUTPUT | ||||
AC/AC Efficiency (Max.) |
96% |
|||
Power Factor |
1.0 |
|||
Voltage (VAC) |
220/230/240±1% (L-N) 380/400/415±1% (L-L) |
|||
Frequency (Hz) |
50/60±0.1 (battery mode) |
|||
THDv |
THD <1% (linear load), THD <3% (nonlinear load) |
|||
Crest Factor |
3:1 |
|||
Overload¹ |
110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms |
|||
EPO |
Remote and Local |
|||
Coldstart |
Yes |
|||
BATTERY | ||||
Voltage (Vdc) | ±192 (±144 ~±240 adjustable)* | |||
Internal Battery | 48~80×9AH/12V | |||
Charging Current (A) | 1-20 settable | |||
OTHER | ||||
Communication Interface | RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot) | |||
Display | 4.3 Inch Touch Screen+ LED+ Physical buttons | |||
Alarm | Low battery, abnormal AC input, UPS failure, etc. | |||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||
Noise (dB) | <55 | |||
Working Temperature | -5~40 | |||
Altitude | 2000, no derate | |||
Relative Humidity | 0 ~ 95%, no condensation | |||
Dimensions (WxDxH) (mm) | 300×785×1250 | |||
Weight |
with battery | 240 (64×9AH) | ||
without battery | 85 | |||
witht TX | 240 | |||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
||||
MODEL |
MY-UP300 40kVA |
|||
INPUT | ||||
Voltage (VAC) |
138-485 (L-L) |
|||
Phase |
3:1/3:3 |
|||
Frequency | 40-70 | |||
Power Factor |
≥0.99 |
|||
THDi |
<3% | |||
Dual Main Input |
Yes |
|||
OUTPUT | ||||
AC/AC Efficiency (Max.) |
96% |
|||
Power Factor |
1.0 |
|||
Voltage (VAC) |
220/230/240±1% (L-N) 380/400/415±1% (L-L) |
|||
Frequency (Hz) |
50/60±0.1 (battery mode) |
|||
THDv |
THD <1% (linear load), THD <3% (nonlinear load) |
|||
Crest Factor |
3:1 |
|||
Overload¹ |
110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms |
|||
EPO |
Remote and Local |
|||
Coldstart |
Yes |
|||
BATTERY | ||||
Voltage (Vdc) | ±192 (±144 ~±240 adjustable)* | |||
Internal Battery | 48~80×9AH/12V | |||
Charging Current (A) | 1-20 settable | |||
OTHER | ||||
Communication Interface | RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot) | |||
Display | 4.3 Inch Touch Screen+ LED+ Physical buttons | |||
Alarm | Low battery, abnormal AC input, UPS failure, etc. | |||
Protection | Low battery, overload, short-circuit and over temperature, etc. | |||
Noise (dB) | <55 | |||
Working Temperature | -5~40 | |||
Altitude | 2000, no derate | |||
Relative Humidity | 0 ~ 95%, no condensation | |||
Dimensions (WxDxH) (mm) | 300×785×1250 | |||
Weight |
with battery | 264 (80×9AH) | ||
without battery | 85 | |||
witht TX | 240 | |||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
- MYUP300 60kVA
- MYUP300 80kVA
- MYUP300 100kVA
- MYUP300 120kVA
- MYUP300 160kVA
- MYUP300 200kVA
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
|||
MODEL |
MY-UP300 60kVA |
||
INPUT | |||
Voltage (VAC) |
380/400/415 (138~485 L-L) |
||
Frequency | 40~70 | ||
Power Factor |
≥0.99 |
||
Phase | 3φ4W+PE | ||
THDi at full linear load |
<3% | ||
BYPASS | |||
Bypass Voltage (Vac) |
380/400/415 |
||
Voltage Range |
+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable) | ||
Overload |
≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately. |
||
OUTPUT | |||
Capacity (kW) |
60 |
||
Power Factor |
1 (0.5 leading to 0.5 lagging) |
||
Voltage (VAC) |
380/400/415±1% |
||
Frequency (Hz) |
(Hz) 50/60±0.1% (Battery mode) |
||
Phase |
3φ4W+PE | ||
Three Phase Difference |
≤1% |
||
Waveform |
Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load |
||
Transfer Time (ms) |
0 |
||
AC-AC Efficiency |
up to 96.5% |
||
Overload | 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass |
||
BATTERY | |||
Voltage (Vdc) | ±192(±168 ~±288 adjustable) |
||
Battery Type |
External | ||
Charging Current (A) MAX | 30 | ||
OTHER | |||
Communication Interface | RS232, RS485, MODBUS, dry contact |
||
Display | 4.3" Touch screen+LED+LED bar | ||
Alarm | AC input abnormal, low battery, overload, failure | ||
Protection | Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage | ||
Noise (dB) | <65 | ||
Altitude | 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase |
||
IP | IP20 | ||
Working Temperature (°C) | 0 ~ 40 no derate,40~50 auto derate. | ||
Relative Humidity | 0 ~ 95%, no condensation |
||
Dimensions (WxDxH) (mm) | 400×960×1200 | ||
Weight Kg) |
145 | ||
• Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
|||
MODEL |
MY-UP300 80kVA |
||
INPUT | |||
Voltage (VAC) |
380/400/415 (138~485 L-L) |
||
Frequency | 40~70 | ||
Power Factor |
≥0.99 |
||
Phase | 3φ4W+PE | ||
THDi at full linear load |
<3% | ||
BYPASS | |||
Bypass Voltage (Vac) |
380/400/415 |
||
Voltage Range |
+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable) | ||
Overload |
≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately. |
||
OUTPUT | |||
Capacity (kW) |
80 |
||
Power Factor |
1 (0.5 leading to 0.5 lagging) |
||
Voltage (VAC) |
380/400/415±1% |
||
Frequency (Hz) |
(Hz) 50/60±0.1% (Battery mode) |
||
Phase |
3φ4W+PE | ||
Three Phase Difference |
≤1% |
||
Waveform |
Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load |
||
Transfer Time (ms) |
0 |
||
AC-AC Efficiency |
up to 96.5% |
||
Overload | 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass |
||
BATTERY | |||
Voltage (Vdc) | ±192(±168 ~±288 adjustable) |
||
Battery Type |
External | ||
Charging Current (A) MAX | 30 | ||
OTHER | |||
Communication Interface | RS232, RS485, MODBUS, dry contact |
||
Display | 4.3" Touch screen+LED+LED bar | ||
Alarm | AC input abnormal, low battery, overload, failure | ||
Protection | Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage | ||
Noise (dB) | <65 | ||
Altitude | 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase |
||
IP | IP20 | ||
Working Temperature (°C) | 0 ~ 40 no derate,40~50 auto derate. | ||
Relative Humidity | 0 ~ 95%, no condensation |
||
Dimensions (WxDxH) (mm) | 400×960×1200 | ||
Weight Kg) |
161 | ||
• Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
|||
MODEL |
MY-UP300 100kVA |
||
INPUT | |||
Voltage (VAC) |
380/400/415 (138~485 L-L) |
||
Frequency | 40~70 | ||
Power Factor |
≥0.99 |
||
Phase | 3φ4W+PE | ||
THDi at full linear load |
<3% | ||
BYPASS | |||
Bypass Voltage (Vac) |
380/400/415 |
||
Voltage Range |
+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable) | ||
Overload |
≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately. |
||
OUTPUT | |||
Capacity (kW) |
100 |
||
Power Factor |
1 (0.5 leading to 0.5 lagging) |
||
Voltage (VAC) |
380/400/415±1% |
||
Frequency (Hz) |
(Hz) 50/60±0.1% (Battery mode) |
||
Phase |
3φ4W+PE | ||
Three Phase Difference |
≤1% |
||
Waveform |
Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load |
||
Transfer Time (ms) |
0 |
||
AC-AC Efficiency |
up to 96.5% |
||
Overload | 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass |
||
BATTERY | |||
Voltage (Vdc) | ±240(±168 ~±288 adjustable) |
||
Battery Type |
External | ||
Charging Current (A) MAX | 30 | ||
OTHER | |||
Communication Interface | RS232, RS485, MODBUS, dry contact |
||
Display | 4.3" Touch screen+LED+LED bar | ||
Alarm | AC input abnormal, low battery, overload, failure | ||
Protection | Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage | ||
Noise (dB) | <70 | ||
Altitude | 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase |
||
IP | IP20 | ||
Working Temperature (°C) | 0 ~ 40 no derate,40~50 auto derate. | ||
Relative Humidity | 0 ~ 95%, no condensation |
||
Dimensions (WxDxH) (mm) | 400×960×1200 | ||
Weight Kg) |
161 | ||
• Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
|||
MODEL |
MY-UP300 120kVA |
||
INPUT | |||
Voltage (VAC) |
380/400/415 (138~485 L-L) |
||
Frequency | 40~70 | ||
Power Factor |
≥0.99 |
||
Phase | 3φ4W+PE | ||
THDi at full linear load |
<3% | ||
BYPASS | |||
Bypass Voltage (Vac) |
380/400/415 |
||
Voltage Range |
+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable) | ||
Overload |
≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately. |
||
OUTPUT | |||
Capacity (kW) |
120 |
||
Power Factor |
1 (0.5 leading to 0.5 lagging) |
||
Voltage (VAC) |
380/400/415±1% |
||
Frequency (Hz) |
(Hz) 50/60±0.1% (Battery mode) |
||
Phase |
3φ4W+PE | ||
Three Phase Difference |
≤1% |
||
Waveform |
Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load |
||
Transfer Time (ms) |
0 |
||
AC-AC Efficiency |
up to 96.5% |
||
Overload | 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass |
||
BATTERY | |||
Voltage (Vdc) | ±240(±168 ~±288 adjustable) |
||
Battery Type |
External | ||
Charging Current (A) MAX | 30 | ||
OTHER | |||
Communication Interface | RS232, RS485, MODBUS, dry contact |
||
Display | 4.3" Touch screen+LED+LED bar | ||
Alarm | AC input abnormal, low battery, overload, failure | ||
Protection | Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage | ||
Noise (dB) | <70 | ||
Altitude | 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase |
||
IP | IP20 | ||
Working Temperature (°C) | 0 ~ 40 no derate,40~50 auto derate. | ||
Relative Humidity | 0 ~ 95%, no condensation |
||
Dimensions (WxDxH) (mm) | 400×960×1200 | ||
Weight Kg) |
161 | ||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
|||
MODEL |
MY-UP300 160kVA |
||
INPUT | |||
Voltage (VAC) |
380/400/415 (138~485 L-L) |
||
Frequency | 40~70 | ||
Power Factor |
≥0.99 |
||
Phase | 3φ4W+PE | ||
THDi at full linear load |
<3% | ||
BYPASS | |||
Bypass Voltage (Vac) |
380/400/415 |
||
Voltage Range |
+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable) | ||
Overload |
≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately. |
||
OUTPUT | |||
Capacity (kW) |
160 |
||
Power Factor |
1 (0.5 leading to 0.5 lagging) |
||
Voltage (VAC) |
380/400/415±1% |
||
Frequency (Hz) |
(Hz) 50/60±0.1% (Battery mode) |
||
Phase |
3φ4W+PE | ||
Three Phase Difference |
≤1% |
||
Waveform |
Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load |
||
Transfer Time (ms) |
0 |
||
AC-AC Efficiency |
up to 96.5% |
||
Overload | 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass |
||
BATTERY | |||
Voltage (Vdc) | ±240(±168 ~±288 adjustable) |
||
Battery Type |
External | ||
Charging Current (A) MAX | 60 | ||
OTHER | |||
Communication Interface | RS232, RS485, MODBUS, dry contact |
||
Display | 7" Touch screen+LED+LED bar | ||
Alarm | AC input abnormal, low battery, overload, failure | ||
Protection | Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage | ||
Noise (dB) | <70 | ||
Altitude | 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase |
||
IP | IP20 | ||
Working Temperature (°C) | 0 ~ 40 no derate,40~50 auto derate. | ||
Relative Humidity | 0 ~ 95%, no condensation |
||
Dimensions (WxDxH) (mm) | 600×1000×1600 | ||
Weight Kg) |
312 | ||
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice |
MY-UP300 SERIES TECHNICAL SPECIFICATIONS |
|||
MODEL |
MY-UP300 200kVA |
||
INPUT | |||
Voltage (VAC) |
380/400/415 (138~485 L-L) |
||
Frequency | 40~70 | ||
Power Factor |
≥0.99 |
||
Phase | 3φ4W+PE | ||
THDi at full linear load |
<3% | ||
BYPASS | |||
Bypass Voltage (Vac) |
380/400/415 |
||
Voltage Range |
+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable) | ||
Overload |
≤130%: long run; 130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately. |
||
OUTPUT | |||
Capacity (kW) |
200 |
||
Power Factor |
1 (0.5 leading to 0.5 lagging) |
||
Voltage (VAC) |
380/400/415±1% |
||
Frequency (Hz) |
(Hz) 50/60±0.1% (Battery mode) |
||
Phase |
3φ4W+PE | ||
Three Phase Difference |
≤1% |
||
Waveform |
Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load |
||
Transfer Time (ms) |
0 |
||
AC-AC Efficiency |
up to 96.5% |
||
Overload | 101-105% Long run, 106-110% load for 60 minutes, 111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass |
||
BATTERY | |||
Voltage (Vdc) | ±240(±168 ~±288 adjustable) |
||
Battery Type |
External | ||
Charging Current (A) MAX | 60 | ||
OTHER | |||
Communication Interface | RS232, RS485, MODBUS, dry contact |
||
Display | 7" Touch screen+LED+LED bar | ||
Alarm | AC input abnormal, low battery, overload, failure | ||
Protection | Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage | ||
Noise (dB) | <70 | ||
Altitude | 0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase |
||
IP | IP20 | ||
Working Temperature (°C) | 0 ~ 40 no derate,40~50 auto derate. | ||
Relative Humidity | 0 ~ 95%, no condensation |
||
Dimensions (WxDxH) (mm) | 600×1000×1600 | ||
Weight Kg) |
312 | ||
• Specification is subject to change without prior notice |