3 Phase online UPS

UPS | MY-UP300 SERIES 10-200 kVA

3 Phase: 10kVA - 200kVA

Firstly the NEW 3-phase MY-UP300 Series offers excellent protection against energy quality problems in addition to using the latest technologies to improve performance and security. Secondly it has wide input voltage and frequency range as well as high grid adaptability and finally prolonged battery life, all making this UPS reliable and extremely powerful. The advanced dual DSP control prevents single failure point and increases its performance.

Areas of Usage

Telecoms
Local Area Networks
E-business
Data Centre
Point of Sale
Security

REQUEST A QUOTE

SHARE

  • Adjustable input and output configuration.
  • High AC/AC efficiency up to 96%.
  • High output power factor up to 1.0.
  • Common battery bank.
  • Optional 4.3 inch touch screen

The 3-phase MY-UP300 series is a modern high-frequency design UPS is suitable for a wide range of applications such as telecoms, local area networks, e-business, data-centres, cash registers and security.  

The 3-Phase MY-UP300 series conforms to the following standards:

ISO9001
ISO14001
ISO45001 

GENERAL SPECIFICATIONS:

  • Super wide input voltage range -60%~+25% for higher grid adaptability
  • Dual DSP control for top performance
  • Intelligent fan speed control reduces noise and prolongs fan life
  • Anti-corrosion resistant coating for all PCB boards
  • Full protection with input, output, bypass, maintenance bypass and battery breaker
  • ECO mode and EPO function
  • AC/AC efficiency up to 96%, less TCO and more energy saving
  • Output power factor up to 1.0, more powerful to connect more critical loads
  • 3 level IGBT technology for higher efficiency and
    minimized interference to grid.
  • Adjustable input and output
  • Built-in battery and flexible battery configuration
  • Common battery bank
  • Easy onsite parallel slot modification
  • Wheel design
  • Options are displayed in 7 languages: English, Russian,
    Chinese, Spanish, Polish, Italian and Korean

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 10kVA

INPUT

Voltage (VAC)

80-280 (L-N)/138-485 (L-L)

Phase

1:1/3:1/3:3

Frequency 40-70

Power Factor

≥0.99

THDi

<3%

Dual Main Input

Yes

OUTPUT

AC/AC Efficiency (Max.)

96%

Power Factor

1.0

Voltage (VAC)

220/230/240±1% (L-N) 380/400/415±1% (L-L)

Frequency (Hz)

50/60±0.1 (battery mode)

THDv

THD <1% (linear load),
THD <3% (nonlinear load)

Crest Factor

3:1

Overload¹

110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms

EPO

Remote and Local

Coldstart

Yes

BATTERY
Voltage (Vdc) ±192 (±96 ~±240 adjustable)
Internal Battery 16~40×9AH/12V
Charging Current (A) 1-10 settable
OTHER
Communication Interface RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot)
Display 4.3 Inch Touch Screen+ LED+ Physical buttons
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) <55
Working Temperature -5~40
Altitude 2000, no derate
Relative Humidity 0 ~ 95%, no condensation
Dimensions (WxDxH) (mm) 250×755×880

Weight
(Kg)

with battery 98 (20×7AH)
without battery 50
witht TX 143
* Capacity will derate when battery voltage between ±144~±180
• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 15kVA

INPUT

Voltage (VAC)

80-280 (L-N)/138-485 (L-L)

Phase

1:1/3:1/3:3

Frequency 40-70

Power Factor

≥0.99

THDi

<3%

Dual Main Input

Yes

OUTPUT

AC/AC Efficiency (Max.)

96%

Power Factor

1.0

Voltage (VAC)

220/230/240±1% (L-N) 380/400/415±1% (L-L)

Frequency (Hz)

50/60±0.1 (battery mode)

THDv

THD <1% (linear load), THD <3% (nonlinear load)

Crest Factor

3:1

Overload¹

110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms

EPO

Remote and Local

Coldstart

Yes

BATTERY
Voltage (Vdc) ±192 (±144 ~±240 adjustable)*
Internal Battery 24~40×9AH/12V
Charging Current (A) 1-10 settable
OTHER
Communication Interface RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot)
Display 4.3 Inch Touch Screen+ LED+ Physical buttons
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) <55
Working Temperature -5~40
Altitude 2000, no derate
Relative Humidity 0 ~ 95%, no condensation
Dimensions (WxDxH) (mm) 250×755×880
Weight (Kg) with battery 127 (32×9AH)
without battery 50
witht TX 143
* Capacity will derate when battery voltage between ±144~±180 • Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 20kVA

INPUT

Voltage (VAC)

80-280 (L-N)/138-485 (L-L)

Phase

1:1/3:1/3:3

Frequency 40-70

Power Factor

≥0.99

THDi

<3%

Dual Main Input

Yes

OUTPUT

AC/AC Efficiency (Max.)

96%

Power Factor

1.0

Voltage (VAC)

220/230/240±1% (L-N) 380/400/415±1% (L-L)

Frequency (Hz)

50/60±0.1 (battery mode)

THDv

THD <1% (linear load),
THD <3% (nonlinear load)

Crest Factor

3:1

Overload¹

110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms

EPO

Remote and Local

Coldstart

Yes

BATTERY
Voltage (Vdc) ±192 (±144 ~±240 adjustable)*
Internal Battery 24~40×9AH/12V
Charging Current (A) 1-10 settable
OTHER
Communication Interface RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot)
Display 4.3 Inch Touch Screen+ LED+ Physical buttons
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) <55
Working Temperature -5~40
Altitude 2000, no derate
Relative Humidity 0 ~ 95%, no condensation
Dimensions (WxDxH) (mm) 250×755×880

Weight
(Kg)

with battery 144 (40×9AH)
without battery 50
witht TX 143
* Capacity will derate when battery voltage between ±144~±180
• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 30kVA

INPUT

Voltage (VAC)

138-485 (L-L)

Phase

3:1/3:3

Frequency 40-70

Power Factor

≥0.99

THDi

<3%

Dual Main Input

Yes

OUTPUT

AC/AC Efficiency (Max.)

96%

Power Factor

1.0

Voltage (VAC)

220/230/240±1% (L-N) 380/400/415±1% (L-L)

Frequency (Hz)

50/60±0.1 (battery mode)

THDv

THD <1% (linear load),
THD <3% (nonlinear load)

Crest Factor

3:1

Overload¹

110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms

EPO

Remote and Local

Coldstart

Yes

BATTERY
Voltage (Vdc) ±192 (±144 ~±240 adjustable)*
Internal Battery 48~80×9AH/12V
Charging Current (A) 1-20 settable
OTHER
Communication Interface RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot)
Display 4.3 Inch Touch Screen+ LED+ Physical buttons
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) <55
Working Temperature -5~40
Altitude 2000, no derate
Relative Humidity 0 ~ 95%, no condensation
Dimensions (WxDxH) (mm) 300×785×1250

Weight
(Kg)

with battery 240 (64×9AH)
without battery 85
witht TX 240
* Capacity will derate when battery voltage between ±144~±180
• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 40kVA

INPUT

Voltage (VAC)

138-485 (L-L)

Phase

3:1/3:3

Frequency 40-70

Power Factor

≥0.99

THDi

<3%

Dual Main Input

Yes

OUTPUT

AC/AC Efficiency (Max.)

96%

Power Factor

1.0

Voltage (VAC)

220/230/240±1% (L-N) 380/400/415±1% (L-L)

Frequency (Hz)

50/60±0.1 (battery mode)

THDv

THD <1% (linear load),
THD <3% (nonlinear load)

Crest Factor

3:1

Overload¹

110% load for 60 mins, 130% load for 10 mins, 155% load for 1 min, above 155% load for 200ms

EPO

Remote and Local

Coldstart

Yes

BATTERY
Voltage (Vdc) ±192 (±144 ~±240 adjustable)*
Internal Battery 48~80×9AH/12V
Charging Current (A) 1-20 settable
OTHER
Communication Interface RS485+EPO+Dry contact (1 input,5 output)(SNMP are optional in slot)
Display 4.3 Inch Touch Screen+ LED+ Physical buttons
Alarm Low battery, abnormal AC input, UPS failure, etc.
Protection Low battery, overload, short-circuit and over temperature, etc.
Noise (dB) <55
Working Temperature -5~40
Altitude 2000, no derate
Relative Humidity 0 ~ 95%, no condensation
Dimensions (WxDxH) (mm) 300×785×1250

Weight
(Kg)

with battery 264 (80×9AH)
without battery 85
witht TX 240
* Capacity will derate when battery voltage between ±144~±180
• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 60kVA

INPUT

Voltage (VAC)

380/400/415 (138~485 L-L)

Frequency 40~70

Power Factor

≥0.99

Phase 3φ4W+PE

THDi at full linear load

<3%
BYPASS

Bypass Voltage (Vac)

380/400/415

Voltage Range

+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable)

Overload

≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT

Capacity (kW)

60

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (VAC)

380/400/415±1%

Frequency (Hz)

(Hz) 50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

Waveform

Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload 101-105% Long run, 106-110% load for 60 minutes,
111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
BATTERY
Voltage (Vdc)

±192(±168 ~±288 adjustable)

Battery Type
External
Charging Current (A) MAX 30
OTHER
Communication Interface

RS232, RS485, MODBUS, dry contact
( BMS,SNMP, expend dry contact card are optional in slot)

Display 4.3" Touch screen+LED+LED bar
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB) <65
Altitude

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

IP IP20
Working Temperature (°C) 0 ~ 40 no derate,40~50 auto derate.
Relative Humidity

0 ~ 95%, no condensation

Dimensions (WxDxH) (mm) 400×960×1200

Weight Kg)

145

• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 80kVA

INPUT

Voltage (VAC)

380/400/415 (138~485 L-L)

Frequency 40~70

Power Factor

≥0.99

Phase 3φ4W+PE

THDi at full linear load

<3%
BYPASS

Bypass Voltage (Vac)

380/400/415

Voltage Range

+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable)

Overload

≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT

Capacity (kW)

80

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (VAC)

380/400/415±1%

Frequency (Hz)

(Hz) 50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

Waveform

Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload 101-105% Long run, 106-110% load for 60 minutes,
111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
BATTERY
Voltage (Vdc)

±192(±168 ~±288 adjustable)

Battery Type
External
Charging Current (A) MAX 30
OTHER
Communication Interface

RS232, RS485, MODBUS, dry contact
( BMS,SNMP, expend dry contact card are optional in slot)

Display 4.3" Touch screen+LED+LED bar
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB) <65
Altitude

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

IP IP20
Working Temperature (°C) 0 ~ 40 no derate,40~50 auto derate.
Relative Humidity

0 ~ 95%, no condensation

Dimensions (WxDxH) (mm) 400×960×1200

Weight Kg)

161

• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 100kVA

INPUT

Voltage (VAC)

380/400/415 (138~485 L-L)

Frequency 40~70

Power Factor

≥0.99

Phase 3φ4W+PE

THDi at full linear load

<3%
BYPASS

Bypass Voltage (Vac)

380/400/415

Voltage Range

+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable)

Overload

≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT

Capacity (kW)

100

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (VAC)

380/400/415±1%

Frequency (Hz)

(Hz) 50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

Waveform

Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload 101-105% Long run, 106-110% load for 60 minutes,
111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
BATTERY
Voltage (Vdc)

±240(±168 ~±288 adjustable)

Battery Type
External
Charging Current (A) MAX 30
OTHER
Communication Interface

RS232, RS485, MODBUS, dry contact
( BMS,SNMP, expend dry contact card are optional in slot)

Display 4.3" Touch screen+LED+LED bar
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB) <70
Altitude

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

IP IP20
Working Temperature (°C) 0 ~ 40 no derate,40~50 auto derate.
Relative Humidity

0 ~ 95%, no condensation

Dimensions (WxDxH) (mm) 400×960×1200

Weight Kg)

161

• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 120kVA

INPUT

Voltage (VAC)

380/400/415 (138~485 L-L)

Frequency 40~70

Power Factor

≥0.99

Phase 3φ4W+PE

THDi at full linear load

<3%
BYPASS

Bypass Voltage (Vac)

380/400/415

Voltage Range

+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable)

Overload

≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT

Capacity (kW)

120

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (VAC)

380/400/415±1%

Frequency (Hz)

(Hz) 50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

Waveform

Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload 101-105% Long run, 106-110% load for 60 minutes,
111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
BATTERY
Voltage (Vdc)

±240(±168 ~±288 adjustable)

Battery Type
External
Charging Current (A) MAX 30
OTHER
Communication Interface

RS232, RS485, MODBUS, dry contact
( BMS,SNMP, expend dry contact card are optional in slot)

Display 4.3" Touch screen+LED+LED bar
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB) <70
Altitude

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

IP IP20
Working Temperature (°C) 0 ~ 40 no derate,40~50 auto derate.
Relative Humidity

0 ~ 95%, no condensation

Dimensions (WxDxH) (mm) 400×960×1200

Weight Kg)

161
* Capacity will derate when battery voltage between ±144~±180
• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 160kVA

INPUT

Voltage (VAC)

380/400/415 (138~485 L-L)

Frequency 40~70

Power Factor

≥0.99

Phase 3φ4W+PE

THDi at full linear load

<3%
BYPASS

Bypass Voltage (Vac)

380/400/415

Voltage Range

+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable)

Overload

≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT

Capacity (kW)

160

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (VAC)

380/400/415±1%

Frequency (Hz)

(Hz) 50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

Waveform

Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload 101-105% Long run, 106-110% load for 60 minutes,
111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
BATTERY
Voltage (Vdc)

±240(±168 ~±288 adjustable)

Battery Type
External
Charging Current (A) MAX 60
OTHER
Communication Interface

RS232, RS485, MODBUS, dry contact
( BMS,SNMP, expend dry contact card are optional in slot)

Display 7" Touch screen+LED+LED bar
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB) <70
Altitude

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

IP IP20
Working Temperature (°C) 0 ~ 40 no derate,40~50 auto derate.
Relative Humidity

0 ~ 95%, no condensation

Dimensions (WxDxH) (mm) 600×1000×1600

Weight Kg)

312
* Capacity will derate when battery voltage between ±144~±180
• Specification is subject to change without prior notice

MY-UP300 SERIES TECHNICAL SPECIFICATIONS

MODEL

MY-UP300 200kVA

INPUT

Voltage (VAC)

380/400/415 (138~485 L-L)

Frequency 40~70

Power Factor

≥0.99

Phase 3φ4W+PE

THDi at full linear load

<3%
BYPASS

Bypass Voltage (Vac)

380/400/415

Voltage Range

+20% (-10/-15/-30 selectable)/+15% (10/20/25 selectable)

Overload

≤130%: long run;
130%< load ≤150%: 5min; 150%< load ≤200%: 1s; 200%< load≤300%: 100ms; >300%: immediately.
OUTPUT

Capacity (kW)

200

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (VAC)

380/400/415±1%

Frequency (Hz)

(Hz) 50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

Waveform

Pure sine wave, THDv<1% at linear load,THDv<3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload 101-105% Long run, 106-110% load for 60 minutes,
111%-125% load for 10 minutes, 126%-150% load for 1 minute, over 150% load transfer to bypass
BATTERY
Voltage (Vdc)

±240(±168 ~±288 adjustable)

Battery Type
External
Charging Current (A) MAX 60
OTHER
Communication Interface

RS232, RS485, MODBUS, dry contact
( BMS,SNMP, expend dry contact card are optional in slot)

Display 7" Touch screen+LED+LED bar
Alarm AC input abnormal, low battery, overload, failure
Protection Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage
Noise (dB) <70
Altitude

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

IP IP20
Working Temperature (°C) 0 ~ 40 no derate,40~50 auto derate.
Relative Humidity

0 ~ 95%, no condensation

Dimensions (WxDxH) (mm) 600×1000×1600

Weight Kg)

312

• Specification is subject to change without prior notice