UP3000-G4 SERIES

10kVA - 20kVA 3-phase (3-3) UPS online double conversion

The UP3000-G4 series is an advanced three phase, true online, dual conversion, digitally controlled UPS and utilises a transformerless with IGBT rectifier advanced technology and is designed to withstand all types of loads found typically in Telecom, Data Centre, Banking and Laboratory applications.

Areas of Usage

telecoms
data centre
banking
laboratory

REQUEST A QUOTE

SHARE

10kVA – 20kVA 3-3
online double conversion UPS

The UP3000-G4 Series is a 3-phase UPS that is designed to withstand heavy loads found typically in the Telecom, Data Centre, Banking, and Laboratory environments. 

Benefits:

  • 3-3 phase, online Double conversion
  • DSP digital control technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Cold start
  • Dual input
  • Wide input voltage range (190 V ~ 485 V)
  • Auto sensing frequency
  • 50 / 60 Hz frequency conversion mode
  • Work efficiency up to 98% in ECO mode
  • Auto control fan speed when loads varies
  • Flexible battery configuration for using 14/16/18/20 pcs batteries
  • Compact internal layout, miniaturized the complete unit for small footprint
  • LCD+LED display, multi-functional keys operation, friendly human machine interface
  • Doubling the battery charging speed, 90% capacity restored in 4 hours (standard model UPS)
  • Linear derating in low voltage input, reducing battery discharging times, extending the service life of the battery
  • Advanced battery management (ABM), automatic floating / equalising charge control, charger dormancy control
  • Standard emergency power off (EPO)
  • Standard maintenance bypass
  • Standard RS232 / USB communication port
  • Optional N+X redundancy parallel up to 6 units

 

TECHNICAL SPECIFICATIONS UP3000-G4 (10kVA)

MODEL

UP3010-G4

Capacity / Power (kVA)

10kVA / 9kW

INPUT

Related Voltage

360 / 380 / 400 / 415 Vac

Voltage Range

277 ~ 485 VAC (no derating);
190 ~ 277 Vac (linear derating between 50% and 100% load)

Rated Frequency

50Hz / 60Hz (auto-sensing)

Frequency Range

40 ~ 70Hz

Power Factor

≥ 0.99

By-Pass Voltage Range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Rated Voltage

360 / 380 / 400 / 415 Vac (settable)

Voltage regulation

± 1 %

Frequency

45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) 

Waveform

Sinusoidal

Power factor

0.9

Total Harmonic Distortion (THDv)

≤ 2% (linear load); ≤ 5% (non-linear load)

Crest factor

3:1 

Overload (Inverter)

102% ~ 125% for 10 min, 125% ~ 150% for 1 min,> 150% for 0.5 s

Overload (Bypass)

102% ~ 125% for 20 min, 125% ~ 150% for 2 min,> 150% for 1 s

BATTERIES

DC Voltage

Standard model: 240 Vdc; Long time model: 192 Vdc (168 / 192 / 216 / 240V optional)

Charging current

Long time model: 7 A supplied (additional 7 A is optional)
Standard model: 1 A, 2 A, 3.5 A settable

Recharge time

Standard model: 90% capacity restored in 4 hours;
Long time model: depends on the capacity of battery

SYSTEM
Efficiency

≥ 93%, ECO mode 98%

Transfer time

0 ms

Max. number of parallel connections

6

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage,
undervoltage and fan failure

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)

Display

LCD + LED

Standards

EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11,
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, I EC 61000-4-6,
IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2

OTHERS

Operating temperature

0°~ 40°C

Storage Temperature

-25° ~ 55° (without batteries)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤60 dB

Online thermal dissipation

3504 BTU/hr

Dimensions (mm) WxDxH

350 x 655 x 732 (H)

Net weight (kg)

55 (H), 115 (S)

• Derate capacity to 90% when the output voltage is adjusted to 360 Vac.
• S = standard model: H = long time model.
• All specs subject to change without notice.
• Custom-made specifications are acceptable.
TECHNICAL SPECIFICATIONS UP3000-G4 (20kVA)

MODEL

UP3020-G4

Capacity / Power (kVA)

20kVA / 18kW

INPUT

Related Voltage

360 / 380 / 400 / 415 Vac

Voltage Range

277 ~ 485 VAC (no derating);
190 ~ 277 Vac (linear derating between 50% and 100% load)

Rated Frequency

50Hz / 60Hz (auto-sensing)

Frequency Range

40 ~ 70Hz

Power Factor

≥ 0.99

By-Pass Voltage Range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Rated Voltage

360 / 380 / 400 / 415 Vac (settable)

Voltage regulation

± 1 %

Frequency

45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) 

Waveform

Sinusoidal

Power factor

0.9

Total Harmonic Distortion (THDv)

≤ 2% (linear load); ≤ 5% (non-linear load)

Crest factor

3:1 

Overload (Inverter)

102% ~ 125% for 10 min, 125% ~ 150% for 1 min,> 150% for 0.5 s

Overload (Bypass)

102% ~ 125% for 20 min, 125% ~ 150% for 2 min,> 150% for 1 s

BATTERIES

DC Voltage

Standard model: 240 Vdc; Long time model: 192 Vdc (168 / 192 / 216 / 240V optional)

Charging current

Long time model: 7 A supplied (additional 7 A is optional)
Standard model: 1 A, 2 A, 3.5 A settable

Recharge time

Standard model: 90% capacity restored in 4 hours;
Long time model: depends on the capacity of battery

SYSTEM
Efficiency

≥ 93%, ECO mode 98%

Transfer time

0 ms

Max. number of parallel connections

6

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage,
undervoltage and fan failure

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)

Display

LCD + LED

Standards

EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11,
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, I EC 61000-4-6,
IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2

OTHERS

Operating temperature

0°~ 40°C

Storage Temperature

-25° ~ 55° (without batteries)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤65 dB

Online thermal dissipation

8281 BTU/hr

Dimensions (mm) WxDxH

350 x 655 x 732 (H)

Net weight (kg)

61 (H), 175 (S)

• Derate capacity to 90% when the output voltage is adjusted to 360 Vac.
• S = standard model: H = long time model.
• All specs subject to change without notice.
• Custom-made specifications are acceptable.