UP3000-G4 SERIES
10kVA - 20kVA 3-phase (3-3) UPS online double conversion
The UP3000-G4 series is an advanced three phase, true online, dual conversion, digitally controlled UPS and utilises a transformerless with IGBT rectifier advanced technology and is designed to withstand all types of loads found typically in Telecom, Data Centre, Banking and Laboratory applications.
Areas of Usage
- General Description
- Technical Specifications
- Documents
10kVA – 20kVA 3-3 The UP3000-G4 Series is a 3-phase UPS that is designed to withstand heavy loads found typically in the Telecom, Data Centre, Banking, and Laboratory environments. Benefits:
|
- UP3000-G4 (10kVA)
- UP3000-G4 (20 kVA)
TECHNICAL SPECIFICATIONS UP3000-G4 (10kVA) | |
MODEL |
UP3010-G4 |
Capacity / Power (kVA) |
10kVA / 9kW |
INPUT | |
Related Voltage |
360 / 380 / 400 / 415 Vac |
Voltage Range |
277 ~ 485 VAC (no derating); |
Rated Frequency |
50Hz / 60Hz (auto-sensing) |
Frequency Range |
40 ~ 70Hz |
Power Factor |
≥ 0.99 |
By-Pass Voltage Range |
– 40% ~ +15% (settable) |
THDi (Total Harmonic Distortion) |
≤ 5% |
OUTPUT | |
Rated Voltage |
360 / 380 / 400 / 415 Vac (settable) |
Voltage regulation |
± 1 % |
Frequency |
45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) |
Waveform |
Sinusoidal |
Power factor |
0.9 |
Total Harmonic Distortion (THDv) |
≤ 2% (linear load); ≤ 5% (non-linear load) |
Crest factor |
3:1 |
Overload (Inverter) |
102% ~ 125% for 10 min, 125% ~ 150% for 1 min,> 150% for 0.5 s |
Overload (Bypass) |
102% ~ 125% for 20 min, 125% ~ 150% for 2 min,> 150% for 1 s |
BATTERIES | |
DC Voltage |
Standard model: 240 Vdc; Long time model: 192 Vdc (168 / 192 / 216 / 240V optional) |
Charging current |
Long time model: 7 A supplied (additional 7 A is optional) |
Recharge time |
Standard model: 90% capacity restored in 4 hours; |
SYSTEM | |
Efficiency |
≥ 93%, ECO mode 98% |
Transfer time |
0 ms |
Max. number of parallel connections |
6 |
Protections |
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, |
Communications |
RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) |
Display |
LCD + LED |
Standards |
EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11, |
OTHERS | |
Operating temperature |
0°~ 40°C |
Storage Temperature |
-25° ~ 55° (without batteries) |
Relative humidity |
0 ~ 95% (non-condensing) |
Altitude |
≤ 1000 m, derating 1% for each additional 100 m |
IP Rating |
IP 20 |
Noise level at 1 m |
≤60 dB |
Online thermal dissipation |
3504 BTU/hr |
Dimensions (mm) WxDxH |
350 x 655 x 732 (H) |
Net weight (kg) |
55 (H), 115 (S) |
• Derate capacity to 90% when the output voltage is adjusted to 360 Vac. • S = standard model: H = long time model. • All specs subject to change without notice. • Custom-made specifications are acceptable. |
TECHNICAL SPECIFICATIONS UP3000-G4 (20kVA) | |
MODEL | UP3020-G4 |
Capacity / Power (kVA) | 20kVA / 18kW |
INPUT | |
Related Voltage | 360 / 380 / 400 / 415 Vac |
Voltage Range | 277 ~ 485 VAC (no derating); |
Rated Frequency | 50Hz / 60Hz (auto-sensing) |
Frequency Range | 40 ~ 70Hz |
Power Factor | ≥ 0.99 |
By-Pass Voltage Range | – 40% ~ +15% (settable) |
THDi (Total Harmonic Distortion) | ≤ 5% |
OUTPUT | |
Rated Voltage | 360 / 380 / 400 / 415 Vac (settable) |
Voltage regulation | ± 1 % |
Frequency | 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) |
Waveform | Sinusoidal |
Power factor | 0.9 |
Total Harmonic Distortion (THDv) | ≤ 2% (linear load); ≤ 5% (non-linear load) |
Crest factor | 3:1 |
Overload (Inverter) | 102% ~ 125% for 10 min, 125% ~ 150% for 1 min,> 150% for 0.5 s |
Overload (Bypass) | 102% ~ 125% for 20 min, 125% ~ 150% for 2 min,> 150% for 1 s |
BATTERIES | |
DC Voltage | Standard model: 240 Vdc; Long time model: 192 Vdc (168 / 192 / 216 / 240V optional) |
Charging current | Long time model: 7 A supplied (additional 7 A is optional) |
Recharge time | Standard model: 90% capacity restored in 4 hours; |
SYSTEM | |
Efficiency | ≥ 93%, ECO mode 98% |
Transfer time | 0 ms |
Max. number of parallel connections | 6 |
Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, |
Communications | RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) |
Display | LCD + LED |
Standards | EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11, |
OTHERS | |
Operating temperature | 0°~ 40°C |
Storage Temperature | -25° ~ 55° (without batteries) |
Relative humidity | 0 ~ 95% (non-condensing) |
Altitude | ≤ 1000 m, derating 1% for each additional 100 m |
IP Rating | IP 20 |
Noise level at 1 m | ≤65 dB |
Online thermal dissipation | 8281 BTU/hr |
Dimensions (mm) WxDxH | 350 x 655 x 732 (H) |
Net weight (kg) | 61 (H), 175 (S) |
• Derate capacity to 90% when the output voltage is adjusted to 360 Vac. • S = standard model: H = long time model. • All specs subject to change without notice. • Custom-made specifications are acceptable. |