UP2000-G4 SERIES

10kVA – 20kVA 3-1 (1-1) phase UPS

The UP2000-G4 series is an advanced single phase, true online, dual conversion, digitally controlled UPS and utilises a transformerless with IGBT rectifier advanced technology and is designed to withstand all types of loads found typically in Telecom, Data Centre, Banking and Laboratory applications.

Areas of Usage

telecoms
data centre
banking
laboratory

REQUEST A QUOTE

SHARE

10kVA – 20kVA 3-1 (1-1) phase UPS

1 Phase Input / 1 Phase Output / or 3 Phase Input / 1 Phase Output 10-20 kVA.

Benefits: 

  • High efficiency 95% (up to 98% in ECO mode).
  • TUV, CE, ISO9001 & ISO14001 certified = proven reliability
  • Engineered for Business
  • Flexibility
  • Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%

Key Features:

  • 3-level technology
  • DSP (Digital Signal Processing) Control
  • Two-year onsite warranty as standard
  • Ten-year guarantee on spares availability
  • Smart and user-friendly LCD interface

TECHNICAL SPECIFICATIONS (UP2010-G4 10kVA)

MODEL

UP2010-G4 – 10kVA

Capacity

10 kVA / 10 kW

INPUT

Input wiring

Three-phase five-wire (3Φ + N + PE)

Rated Voltage

380 / 400 / 415 Vac

Voltage range

190 ~ 305 Vac (linear derating between 50% and 100% load);305 ~ 499 Vac (no derating)

Rated frequency

50 / 60 Hz (auto-sensing)

Frequency range

40Hz – 70Hz

Power factor

> 0.99

By-pass voltage range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Output wiring

Single-phase three-wire (1Φ + N + PE)

Rated voltage

208 (PF=0.9) / 220 / 230 / 240 Vac

Voltage regulation

± 1%

Frequency

Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode

Waveform

Sinusoidal

Power factor

1

THDv (Total Harmonic Distortion)

≤ 1% (linear load); ≤ 3% (non-linear load)

Crest factor

3:1

Overload

105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s

BATTERY

DC voltage

192 Vdc (192 ~ 240 Vdc settable)

Number of batteries

16 pcs (16 ~ 20 settable)

Inbuilt battery (standard model)

12 V / 9 Ah×16

Charging current

Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional, PF0.9)

Recharge time

Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery

SYSTEM

Efficiency

≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure

Max. number of parallel connections

4

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)

Display

LCD + LED

OTHERS

Operating temperature

0°~ 40°

Storage Temperature

-25° ~ 55° (without battery)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤ 58 dB

Dimensions (mm) HxWxD

191 × 495 × 711 (S) 191 × 495 × 350 (H)

Packaged Dimensions (mm)
(W x D x H)

310 × 685 × 941 (S) 318 × 617 × 475 (H)

Net weight (kg)

64 (S), 18.5 (H)

Gross weight (kg)

72 (S), 20 (H)

S = standard model: H = long time model.
All specs subject to change without notice.

TECHNICAL SPECIFICATIONS (UP2015-G4 15kVA)

MODEL

UP2015-G4 – 15kVA

Capacity

15 kVA / 15 kW

INPUT

Input wiring

Three-phase five-wire (3Φ + N + PE)

Rated Voltage

380 / 400 / 415 Vac

Voltage range

190 ~ 305 Vac (linear derating between 50% and 100% load);305 ~ 499 Vac (no derating)

Rated frequency

50 / 60 Hz (auto-sensing)

Frequency range

40Hz – 70Hz

Power factor

> 0.99

By-pass voltage range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Output wiring

Single-phase three-wire (1Φ + N + PE)

Rated voltage

208 (PF=0.9) / 220 / 230 / 240 Vac

Voltage regulation

± 1%

Frequency

Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode

Waveform

Sinusoidal

Power factor

1

THDv (Total Harmonic Distortion)

≤ 1% (linear load); ≤ 3% (non-linear load)

Crest factor

3:1

Overload

105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s

BATTERY

DC voltage

192 Vdc (192 ~ 240 Vdc settable)

Number of batteries

16 pcs (16 ~ 20 settable)

Inbuilt battery (standard model)

/

Charging current

Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional, PF0.9)

Recharge time

Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery

SYSTEM

Efficiency

≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure

Max. number of parallel connections

4

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)

Display

LCD + LED

OTHERS

Operating temperature

0°~ 40°

Storage Temperature

-25° ~ 55° (without battery)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤ 58 dB

Dimensions (mm) HxWxD

191 × 495 × 515 (H)

Packaged Dimensions (mm)
(W x D x H)

285 × 593 × 618 (H)

Net weight (kg)

26.5 (H)

Gross weight (kg)

28 (H)

S = standard model: H = long time model.
All specs subject to change without notice.

TECHNICAL SPECIFICATIONS (UP2020-G4 20kVA)

MODEL

UP2020-G4 – 20kVA

Capacity

20 kVA / 20 kW

INPUT

Input wiring

Three-phase five-wire (3Φ + N + PE)

Rated Voltage

380 / 400 / 415 Vac

Voltage range

190 ~ 305 Vac (linear derating between 50% and 100% load);305 ~ 499 Vac (no derating)

Rated frequency

50 / 60 Hz (auto-sensing)

Frequency range

40Hz – 70Hz

Power factor

> 0.99

By-pass voltage range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Output wiring

Single-phase three-wire (1Φ + N + PE)

Rated voltage

208 (PF=0.9) / 220 / 230 / 240 Vac

Voltage regulation

± 1%

Frequency

Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode

Waveform

Sinusoidal

Power factor

1

THDv (Total Harmonic Distortion)

≤ 1% (linear load); ≤ 3% (non-linear load)

Crest factor

3:1

Overload

105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s

BATTERY

DC voltage

192 Vdc (192 ~ 240 Vdc settable)

Number of batteries

16 pcs (16 ~ 20 settable)

Inbuilt battery (standard model)

/

Charging current

Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional, PF0.9)

Recharge time

Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery

SYSTEM

Efficiency

≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure

Max. number of parallel connections

4

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)

Display

LCD + LED

OTHERS

Operating temperature

0°~ 40°

Storage Temperature

-25° ~ 55° (without battery)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤ 58 dB

Dimensions (mm) HxWxD

191 × 495 × 515 (H)

Packaged Dimensions (mm)
(W x D x H)

285 × 593 × 618 (H)

Net weight (kg)

26.5 (H)

Gross weight (kg)

28 (H)

S = standard model: H = long time model.
All specs subject to change without notice.