UP2000-G4 SERIES

10kVA – 20kVA 3-1 (1-1) phase UPS

The UP2000-G4 series is an advanced single phase, true online, dual conversion, digitally controlled UPS and utilises a transformerless with IGBT rectifier advanced technology and is designed to withstand all types of loads found typically in Telecom, Data Centre, Banking and Laboratory applications.

Areas of Usage

telecoms-icon.gif
telecoms
data-centre-icon.gif
data centre
banking-icon.gif
banking
laboratory-blue-icon.gif
laboratory
UP2000_big.jpg

REQUEST A QUOTE

SHARE

10kVA – 20kVA 3-1 (1-1) phase UPS

1 Phase Input / 1 Phase Output / or 3 Phase Input / 1 Phase Output 10-20 kVA.

Benefits: 

  • High efficiency 95% (up to 98% in ECO mode).
  • TUV, CE, ISO9001 & ISO14001 certified = proven reliability
  • Engineered for Business
  • Flexibility
  • Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%

Key Features:

  • 3-level technology
  • DSP (Digital Signal Processing) Control
  • Two-year onsite warranty as standard
  • Ten-year guarantee on spares availability
  • Smart and user-friendly LCD interface

TECHNICAL SPECIFICATIONS (UP2010-G4 10kVA)

MODEL

UP2010-G4 – 10kVA

Capacity

10 kVA / 10 kW

INPUT

Input wiring

Three-phase five-wire (3Φ + N + PE)

Rated Voltage

380 / 400 / 415 Vac

Voltage range

190 ~ 305 Vac (linear derating between 50% and 100% load);305 ~ 499 Vac (no derating)

Rated frequency

50 / 60 Hz (auto-sensing)

Frequency range

40Hz – 70Hz

Power factor

> 0.99

By-pass voltage range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Output wiring

Single-phase three-wire (1Φ + N + PE)

Rated voltage

208 (PF=0.9) / 220 / 230 / 240 Vac

Voltage regulation

± 1%

Frequency

Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode

Waveform

Sinusoidal

Power factor

1

THDv (Total Harmonic Distortion)

≤ 1% (linear load); ≤ 3% (non-linear load)

Crest factor

3:1

Overload

105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s

BATTERY

DC voltage

192 Vdc (192 ~ 240 Vdc settable)

Number of batteries

16 pcs (16 ~ 20 settable)

Inbuilt battery (standard model)

12 V / 9 Ah×16

Charging current

Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional, PF0.9)

Recharge time

Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery

SYSTEM

Efficiency

≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure

Max. number of parallel connections

4

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)

Display

LCD + LED

OTHERS

Operating temperature

0°~ 40°

Storage Temperature

-25° ~ 55° (without battery)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤ 58 dB

Dimensions (mm) HxWxD

191 × 495 × 711 (S) 191 × 495 × 350 (H)

Packaged Dimensions (mm)
(W x D x H)

310 × 685 × 941 (S) 318 × 617 × 475 (H)

Net weight (kg)

64 (S), 18.5 (H)

Gross weight (kg)

72 (S), 20 (H)

S = standard model: H = long time model.
All specs subject to change without notice.

TECHNICAL SPECIFICATIONS (UP2015-G4 15kVA)

MODEL

UP2015-G4 – 15kVA

Capacity

15 kVA / 15 kW

INPUT

Input wiring

Three-phase five-wire (3Φ + N + PE)

Rated Voltage

380 / 400 / 415 Vac

Voltage range

190 ~ 305 Vac (linear derating between 50% and 100% load);305 ~ 499 Vac (no derating)

Rated frequency

50 / 60 Hz (auto-sensing)

Frequency range

40Hz – 70Hz

Power factor

> 0.99

By-pass voltage range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Output wiring

Single-phase three-wire (1Φ + N + PE)

Rated voltage

208 (PF=0.9) / 220 / 230 / 240 Vac

Voltage regulation

± 1%

Frequency

Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode

Waveform

Sinusoidal

Power factor

1

THDv (Total Harmonic Distortion)

≤ 1% (linear load); ≤ 3% (non-linear load)

Crest factor

3:1

Overload

105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s

BATTERY

DC voltage

192 Vdc (192 ~ 240 Vdc settable)

Number of batteries

16 pcs (16 ~ 20 settable)

Inbuilt battery (standard model)

/

Charging current

Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional, PF0.9)

Recharge time

Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery

SYSTEM

Efficiency

≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure

Max. number of parallel connections

4

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)

Display

LCD + LED

OTHERS

Operating temperature

0°~ 40°

Storage Temperature

-25° ~ 55° (without battery)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤ 58 dB

Dimensions (mm) HxWxD

191 × 495 × 515 (H)

Packaged Dimensions (mm)
(W x D x H)

285 × 593 × 618 (H)

Net weight (kg)

26.5 (H)

Gross weight (kg)

28 (H)

S = standard model: H = long time model.
All specs subject to change without notice.

TECHNICAL SPECIFICATIONS (UP2020-G4 20kVA)

MODEL

UP2020-G4 – 20kVA

Capacity

20 kVA / 20 kW

INPUT

Input wiring

Three-phase five-wire (3Φ + N + PE)

Rated Voltage

380 / 400 / 415 Vac

Voltage range

190 ~ 305 Vac (linear derating between 50% and 100% load);305 ~ 499 Vac (no derating)

Rated frequency

50 / 60 Hz (auto-sensing)

Frequency range

40Hz – 70Hz

Power factor

> 0.99

By-pass voltage range

– 40% ~ +15% (settable)

THDi (Total Harmonic Distortion)

≤ 5%

OUTPUT

Output wiring

Single-phase three-wire (1Φ + N + PE)

Rated voltage

208 (PF=0.9) / 220 / 230 / 240 Vac

Voltage regulation

± 1%

Frequency

Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode

Waveform

Sinusoidal

Power factor

1

THDv (Total Harmonic Distortion)

≤ 1% (linear load); ≤ 3% (non-linear load)

Crest factor

3:1

Overload

105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s

BATTERY

DC voltage

192 Vdc (192 ~ 240 Vdc settable)

Number of batteries

16 pcs (16 ~ 20 settable)

Inbuilt battery (standard model)

/

Charging current

Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 10 A (optional, PF0.9)

Recharge time

Standard model: 90% capacity restored in 8 hours;
Long time model: depend on the capacity of battery

SYSTEM

Efficiency

≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode

Transfer time

0 ms

Protections

Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure

Max. number of parallel connections

4

Communications

RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)

Display

LCD + LED

OTHERS

Operating temperature

0°~ 40°

Storage Temperature

-25° ~ 55° (without battery)

Relative humidity

0 ~ 95% (non-condensing)

Altitude

≤ 1000 m, derating 1% for each additional 100 m

IP Rating

IP 20

Noise level at 1 m

≤ 58 dB

Dimensions (mm) HxWxD

191 × 495 × 515 (H)

Packaged Dimensions (mm)
(W x D x H)

285 × 593 × 618 (H)

Net weight (kg)

26.5 (H)

Gross weight (kg)

28 (H)

S = standard model: H = long time model.
All specs subject to change without notice.