UPS | UP903

3kVA (1-1) phase UPS

The UP903 is a single-phase, true-online UPS,  which offers high efficiency of 92% and high power availability of with an output power factor of 0.9. The intuitive LCD display facilitates easy monitoring of UPS, utility and load parameters.

 

Areas of Usage

servers-icon.gif
servers
workstations-icon.gif
workstations
CCTV-icon.gif
CCTV
laboratory-green-icon.gif
laboratory
POS-icon.gif
POS

REQUEST A QUOTE

SHARE

UP903 Single Phase UPS – 3kVA 

The UP903 is a true-online UPS,  which offers high efficiency of 92% and high power availability with an output power factor of 0.9. The intuitive LCD display facilitates easy monitoring of UPS, utility and load parameters.

  • True on-line double conversion technology
  • DSP control technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Wide input voltage range (110V – 300 Vac) and frequency range (40 – 70 Hz)
  • Auto sensing frequency
  • 50 / 60 Hz frequency conversion
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Quick and stable charging, 90% capacity restored in 3 h (standard model UPS)
  • Settable delayed start when power is restored
  • Advanced battery management (ABM)
  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode
  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)

TECHNICAL SPECIFICATIONS UP903 | 3kVA

 

MODEL

UP903

 

Capacity

3 kVA / 2700 W

INPUT

 

Rated Voltage

208 V / 220 V / 230 V / 240 Vac

 

Voltage range

110 – 176Vac ( linear derating between 50% and 100% load); 176 – 280 Vac (no derating); 280 – 300Vac (derating 50%)

 

Frequency

45 – 55 Hz or 55 – 65 Hz (synchronized range); 50 / 60 Hz + 0.1 Hz {battery mode)

 

Power factor

≥0.99

 

By-pass voltage range

– 25% ~ +15% (settable)

OUTPUT

 

Voltage

208 VI 220 V / 230 V / 240 Vac (settable via LCD)

 

Voltage regulation

± 1%

 

Frequency

45 – 55 Hz or 55 – 65 Hz (synchronized range); 50 / 60 Hz + 0.1 Hz (battery mode)

 

Waveform

Sinusoidal

 

Crest Factor

3:1
 

Harmonic distortion

≤ 2% (linear load); ≤ 5% (non-linear load)

  Transfer time

Mains mode to battery mode: Oms
Inverter mode to bypass mode: 4 ms (typical)

  Overload

105% – 125% for 1 min, 125% – 150% for 30 s, > 150% for 300 ms

EFFICIENCY

 

Mains Mode

≥ 92%

 

Battery Mode

≥ 87%

  ECO Mode ≥ 97%

BATTERIES

 

DC voltage

72V

 

Inbuilt battery

6 x 9 Ah

 

Charging Current (max.)

1 A

 

Recharge time

8 h

 

LCD

Load level, Battery level, AC mode, Battery mode and Fault indicators

ALARMS

 

Utility failure

4 s per beep

 

Low battery

1 s per beep

 

Overload

1 s twice per beep

 

UPS fault

Long beep

OTHERS

 

Communications

RS232 (standard), USB / RS485 / dry contacts/ SNMP (optional)

 

Operating temperature

0 – 40°C

 

Relative Humidity

– 90% (non-condensing)

 

Noise level

≤ 50d B( 1m)

 

Dimensions
WxDxH (mm)

191 x 464 x 335

 

Net Weight (Kgs)

32

 

Gross Weight (Kgs)

34

• Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208 Vac.
• S means standard model, H means long time model.
• AII specifications subject to change without notice.
• Custom-made specifications are acceptable.